By Martynas Vaitaitis, Builder & Project Manager at Vayton. Method checked 21 November 2026.
The room
What it's built from
Heat loss and radiator size
| Radiator, 600 mm high | Length | Gives |
|---|
Radiator BTU questions
How many BTU do I need for a room?
Work out the room's heat loss in watts and multiply by 3.412 to get BTU per hour. A typical London living room of 4 by 3.5 m with solid brick walls and older double glazing loses about 1,100 W, or 3,800 BTU, on a cold day. The same room with insulated cavity walls and new windows loses far less, which is why a calculation per room beats a rule of thumb.
Why does a heat pump need bigger radiators?
A radiator's rating is given at ΔT50, about 70 °C water in a 20 °C room. A boiler runs close to that; a heat pump runs much cooler, around 45 °C, so the same radiator gives roughly half its rated output. To heat the same room, the radiator has to be about twice the size, or the room needs less heat loss.
What temperature is a room designed for?
The usual design temperatures are 21 °C in living rooms, 18 °C in bedrooms, kitchens and halls, and 22 °C in bathrooms, with -2 °C outside for London.
What does the calculator leave out?
Thermal bridges, very large or north-facing glass, chimneys left open and rooms over unheated garages. Treat the answer as a sizing guide; a heating engineer confirms the system, and gas work is done by a Gas Safe registered engineer.